Flanges› Dimensions› AWWA› AWWA C207 Class D› Class D Blind Flange

AWWA C207 Class D
Blind Flange

AWWA C207-18 Class B Ring-Type Slip-On Flange Technical Drawing
DIMENSIONAL DATA
NPS OD of a Flange
(A)
ID of a
Flange (B)
Number of
Bolts
Diameter of
Bolt Circle (C)
Diameter of
Bolts
Thickness of Flange
Class D (T)
4 9.00 4.57 8 7.50 0.625 0.625
5 10.00 5.66 8 8.50 0.750 0.650
6 11.00 6.72 8 9.50 0.750 0.693
8 13.50 8.72 8 11.75 0.750 0.812
10 16.00 10.88 12 14.25 0.875 0.953
12 19.00 12.88 12 17.00 0.875 1.117
14 21.00 14.19 12 18.75 1.000 1.133
16 23.50 16.19 16 21.25 1.000 1.265
18 25.00 18.19 16 22.75 1.125 1.331
20 27.50 20.19 20 25.00 1.125 1.448
22 29.50 22.19 20 27.25 1.250 1.568
24 32.00 24.19 20 29.50 1.250 1.661
26 34.25 24 31.75 1.250 1.786
28 36.50 28 34.00 1.250 1.906
30 38.75 28 36.00 1.250 2.008
32 41.75 28 38.50 1.500 2.150
34 43.75 32 40.50 1.500 2.252
36 46.00 32 42.75 1.500 2.370
38 48.75 32 45.25 1.500 2.506
40 50.75 36 47.25 1.500 2.609
42 53.00 36 49.50 1.500 2.729
44 55.25 40 51.75 1.500 2.849
46 57.25 40 53.75 1.500 2.952
48 59.50 44 56.00 1.500 3.072
50 61.75 44 58.25 1.750 3.196
52 64.00 44 60.50 1.750 3.315
54 66.25 44 62.75 1.750 3.435
60 73.00 52 69.25 1.750 3.779
66 80.00 52 76.00 1.750 4.136
72 86.50 60 82.50 1.750 4.480
TABLE NOTE

1. Ring flanges may be overbored or counterbored to accommodate larger outside-diameter (OD) pipe than shown as nominal. This is done to allow a clear inside diameter (ID) after cement-mortar lining. Wrench clearance between the pipe OD and bolt circle, as well as sufficient gasket seating area, must be maintained.

2. Metric conversion—nominal pipe size: in. × 25 = mm; dimensions: in. × 25.4 = mm; psi × 6.895 = kPa.